Defrost Mode parameters for the SCS Controller

A summary of 'Defrost Mode' parameters for the SCS Controller including the digital display codes, increments and default settings.

The Defrost Cycle can be initiated or terminated by either time or temperature. During the Defrost Cycle the Normal Operational Mode is overridden to control the Compressor, Evaporator Fan, Lights, and if used, any valves or heater elements connected to the Relay. 

Supported Defrost Cycle methods are hot gas defrost (reverse cycle), ambient defrost (with the compressor turned off), and a forced defrost (with an electric heater element). These parameters provide the options to control and configure the Defrost Cycle.

Temperature

Parameter name Digital display Increments & units Range Default
Defrost Initiation Temperature  dIt 1°C -15 to 10°C or dISabled dISabled
Defrost Termination Temperature   dtt  1°C 0 to 30°C 30°C 
Uninterrupted Pull Down 
Temperature* 
Pdn  1 °C  0 to 25 or 
dISabled 
dISabled

* Not available on SCS500 variants


Time


Parameter name Digital display Increments & units Range Default
Maximum Defrost Cycle Time    dCt 1 min 1 to 120 mins  20 mins 
Maximum Defrost Interval   dEI 1 hour 1 to 48 hours  3 hours 
Defrost Type   dtP integers   0 - 3,4** 3
Passive Dripping Time   dPt  1 min 0 to 30 mins  0 min
Active Dripping Time***  dAt  1 min  0 to 30 mins  0 min

** FW Versions 1592 and above
*** FW Versions 4010 and above


Lighting & Display

Parameter name Digital display Increments & units Range Default
Display Value During 
Defrost Cycle# 
ddE integers 3 3
Pre-time For Hot-gas Defrost** n/a 1 min 0 to 240 mins 0 min

** FW Versions 1592 and above
# Not yet implemented