A summary of 'Standby Mode' parameters for the SCS Controller including the digital display codes, increments and default settings.
The Standby Modes are an intelligent method to save power when a cooler is not being used by customers, eg. outside of normal business hours. The SCS Controller uses these modes to minimize the 'Pulldown time' when the business re-opens and to maximize overall energy savings.
If you want to set standby mode based on the time of day and store operating hours, see Time-of-day standby parameters for the SCS Controller.
Temperature
Standby Set Point
Parameter name | Digital display | Increments & units | Range | Default |
Standby Set Point | SSP | 0.1 °C | -10.0 to 20.0 | 8.5 °C |
Standby Differential
Parameter name | Digital display | Increments & units | Range | Default |
Standby Differential | Sd | 0.1 °C | 0.1 to 10.0 | 2.0 °C |
Perishable Mode
Parameter name | Digital display | Increments & units | Range | Default |
Perishable Mode | Per | 0.5 hours | 0.0 to 24.0 | 10.0 hours |
See also Optimise your cooler's power use with Standby Modes for temperature.
Timers & Counters
Maximum Standby Time
Parameter name | Digital display | Increments & units | Range | Default |
Maximum Standby Time | Sbt | 0.5 hours | 0.0 to 24.0 | 10.0 hours |
Pulldown Time
Parameter name | Digital display | Increments & units | Range | Default |
Pulldown Time | Pdt | 0.5 hours | 0.0 to 12.0 | 1.0 hour |
Inactivity Wait Time - Standby Hold
Parameter name | Digital display | Increments & units | Range | Default |
Inactivity Wait Time - Standby Hold | yth | 0.5 hours | 0.0 to 24.0 or inf | 4.0 hours |
See also Optimise your cooler's power use with Standby Modes for timers and counters.
Configuration
Enable Time-of-Day Standby
Parameter name | Digital display | Increments & units | Range | Default |
Enable Time of Day Standby | tdS | integers | 0 to 1 | 0 |
See also Time-of-day standby parameters for the SCS Controller.
Lighting & Display
Light State Standby Modes
Parameter name | Digital display | Increments & units | Range | Default |
Light State Standby Mode - Channel A | LSA | 1 % | 0 to 100 | 0 % |
Light State Standby Mode - Channel B | LSb | 1 % | 0 to 100 | 0 % |
Light State Standby Mode - Channel C | LSC | 1 % | 0 to 100 | 0 % |
Light State Standby Mode - Channel D | LSd | 1 % | 0 to 100 | 0 % |
Light State Standby Mode - Channel E | LSE | integers | 0 to 1 | 0 |
Marketing Mode
Parameter name | Digital display | Increments & units | Range | Default |
Marketing Mode | tnG | text | on or off | off |
* FW versions 4010 and above
^ Not available on SCS500 Variants
* FW Versions 4010 and above
# Not yet implemented