Supply parameters for the SCS Controller

The Supply Parameters configure acceptable limits for Voltage supply to the SCS Controller and configure associated alarms. This protects the refrigeration system from electrical damage.

Maximum Run/Start Compressor Voltage 
The maximum Voltage at which the Compressor is allowed to start and run. After detecting an Over Voltage condition the Compressor is turned off. The minimum compressor off time must be exceeded before the compressor can turn back on. These events are logged in the SCS Controller. 

Digital Display Increments & units Range Default
hPC  1 Vac  100 V to 265 V or disabled  254 Vac 

Minimum Start Compressor Voltage 
The minimum Voltage during which the Compressor is allowed to start. If it is below this Voltage then the Compressor cannot start. If the Voltage rises to an acceptable level then the Compressor can start, but only after the Voltage has been maintained for a delay period. These events are logged in the SCS Controller.

Digital display Increments & units Range Default
LPC  1 Vac  79 V to 203 V or disabled  90 Vac