Normal Mode parameters for the SCS Controller
A summary of 'Normal Mode' parameters for the SCS Controller including the digital display codes, increments, logging (to the Cloud) and default settings.
When running in Normal Mode, the SCS controller primarily operates to maintain the Set Point Temperature.
Temperature
| Parameter name | Digital display | Increments & units | Range | Default |
| Operational Set Point | SP | 0.1 °C | -10.0 to 15.0 °C | 3.5 °C |
| Operational Differential | dIF | 0.1 °C | 0.1 to 10.0 °C | 3.0 °C |
| Maximum User Set Point | SPt | 0.1 °C | -10.0 to 15.0 °C | 6.0 °C |
| Minimum User Set Point | SP- | 0.1 °C | -10.0 to 15.0 °C | 2.0 °C |
Evaporator Fan
| Parameter name | Digital display | Increments & units | Range | Default |
| Evaporator Fan On Time - Normal Mode |
Fot | 1 min | 0 to 30 mins | 2 mins |
| Evaporator Fan Off Time - Normal Mode |
FoF | 1 min | 0 to 30 mins | 2 mins |
Time
| Parameter name | Digital display | Increments & units | Range | Default |
| Inactivity Wait Time - Normal Mode |
Ytn | 0.5 hours | 0.5 to 24 hours or InFinite |
2 hours |
Alarms
| Parameter name | Digital display | Increments & units | Range | Default |
| High Temperature Alarm Setpoint* | htA | 0.1 °C | -10.0 to 15.0 | dISabled |
| Low Temperature Alarm Setpoint* | LtA | 0.1 °C | -5.0 to 20.0 | dISabled |
Operational settings
| Parameter name | Digital display | Increments & units | Range | Default |
| Operational Setpoint | SP | 0.1 °C | -35.0 to 20.0 | 3.5 °C |
| Operational Differential | dIF | 0.1 °C | 0.1 to 10.0 | 3.0 °C |
Lighting & Display
| Parameter name | Digital display | Increments & units | Range | Default |
| Display value during Normal Mode** | - | dlS | intergers | 0 to 3 |
| Light State Normal Mode - Channel A | LnA | 1 % | 0 to 100 | 100 % |
| Light State Normal Mode - Channel B | LnB | 1 % | 0 to 100 | 100 % |
| Light State Normal Mode - Channel C | LnC | 1 % | 0 to 100 | 100 % |
| Light State Normal Mode - Channel D | LnD | 1 % | 0 to 100 | 100 % |
| Light State Normal Mode - Channel E | LnE | integers | 0 to 1 | 1 |
Temperature Alarm Setpoint
| Parameter name | Digital display | Increments & units | Range | Default |
| High Temperature Alarm Setpoint | htA | 0.1 °C | -35.0 to 25.0 or disabled | disabled |
| Low Temperature Alarm Setpoint | LtA | 0.1 °C | -40.0 to 20.0 or disabled | disabled |
| Temperature Out-Of-Spec Alarm Delay | - | 1 min | 1 to 240 | 30 mins |
Logging
The Logging Parameters define how data is logged and sent to the Cloud.
| Parameter name | Digital display | Increments & units | Range | Default |
| Logging interval | LGt | mins | 30 to 1440 | 30 |
*Options 1 & 2 are not functioning
** Not yet implemented