Normal Mode parameters for the SCS Controller

A summary of 'Normal Mode' parameters for the SCS Controller including the digital display codes, increments, logging (to the Cloud) and default settings.


Temperature

Parameter name Digital display Increments & units Range Default
Operational Set Point SP 0.1 °C -10.0 to 15.0 °C 3.5 °C
Operational Differential dIF 0.1 °C 0.1 to 10.0 °C 3.0 °C
Maximum User Set Point SPt 0.1 °C -10.0 to 15.0 °C 6.0 °C
Minimum User Set Point SP- 0.1 °C -10.0 to 15.0 °C 2.0 °C

Evaporator Fan

Parameter name Digital display Increments & units Range Default
Evaporator Fan On 
Time - Normal Mode
Fot 1 min  0 to 30 mins 2 mins 
Evaporator Fan Off 
Time - Normal Mode 
FoF 1 min  0 to 30 mins 2 mins 

Time

Parameter name Digital display Increments & units Range Default
Inactivity Wait 
Time - Normal Mode
Ytn 0.5 hours  0.5 to 24 hours 
or InFinite 
2 hours 

Alarms

Parameter name Digital display Increments & units Range Default
High Temperature Alarm Setpoint* htA  0.1 °C -10.0 to 15.0 dISabled
Low Temperature Alarm Setpoint*  LtA 0.1 °C -5.0 to 20.0 dISabled

Operational settings

Parameter name Digital display Increments & units Range Default
Operational Setpoint SP 0.1 °C -35.0 to 20.0 3.5 °C 
Operational Differential  dIF 0.1 °C 0.1 to 10.0  3.0 °C 

 

Lighting & Display

Parameter name Digital display Increments & units Range Default
Display value during Normal Mode** - dlS intergers 0 to 3 
Light State Normal Mode - Channel A LnA 1 % 0 to 100  100 %
Light State Normal Mode - Channel B LnB 1 % 0 to 100 100 %
Light State Normal Mode - Channel C LnC 1 %  0 to 100 100 %
Light State Normal Mode - Channel D  LnD 1 % 0 to 100 100 % 
Light State Normal Mode - Channel E  LnE integers 0 to 1  1

Temperature Alarm Setpoint

Parameter name Digital display Increments & units Range Default
High Temperature Alarm Setpoint htA 0.1 °C -35.0 to 25.0 or disabled disabled
Low Temperature Alarm Setpoint LtA 0.1 °C -40.0 to 20.0 or disabled disabled 
Temperature Out-Of-Spec Alarm Delay - 1 min 1 to 240 30 mins

Logging

The Logging Parameters define how data is logged and sent to the Cloud.

Parameter name Digital display Increments & units Range Default
Logging interval LGt mins 30 to 1440 30

*Options 1 & 2 are not functioning 

** Not yet implemented